English
简体中文

MWM DEUTZ TBD 604 L6 Marine power station, 372KW-727kW, 1500-1800 RPM

Product Details:

Double circulation cooling

Continuous operation, base load, peak load

Code according to part II of DIN6271

MCXN

Overload capacity

10% according to DIN6271 (7.3.1.1) 1h / 12h

Environmental conditions

Air/Pressurized air cooling medium/atmospheric pressure/relative humidity:

45°C/32°C/0.1MPa

Rotational speed n

r/min

1200

1500

1800

Power Pr

kW

372

480

450

550

540

600

Mean effective pressure

MPa

1.4

1.81

1.36

1.66

1.36

1.51

Average piston speed

m/s

7.8

9.8

11.7

Fuel consumption rate

g/kW.h/

195

190

197

191

202

200

Description:

L MCFN Marine unlimited zone continuous operation fuel limit power, no overload capacity.

L MC20N Marine unlimited zone continuous operation of net effective power, up to 20% overload.

L ICXN ISO net effective power for continuous operation, up to 10% overload.

L ICFN ISO fuel limit power for continuous operation without overload capacity.

L +10% overload 10% power.

L +20% overload 10% power.

L 2H /12h Allows 2 hours of operation within 12 hours.

L 0.5h/6h Allowed to run 0.5 hours within 6 hours.

L 1h/12h Operation within 12 hours is allowed for 1 hour.

L 1000H /a Allows 1000 hours of operation within a year.

Write to us